whatsapp: 0086-18615575385
whatsapp: 0086-13668821631

Adjustment Of Level Sensors Didactic Equipment Vocational Education Equipment Fluid Lab Equipment

Item No.: RT 306
Adjustment Of Level Sensors Didactic Equipment Vocational Education Equipment Fluid Lab Equipment
Description
RT 306 Adjustment Of Level Sensors Didactic Equipment Vocational Education Equipment Fluid Lab Equipment

Familiarisation with different industry standard components with a 4-20mA current loop interface using the example of level measurement
Features
- various measuring principles for level measurement
- industrial 4...20 mA measurement technology
Learning objectives/experiments
- familiarisation with different level sensors
- familiarisation with different industry-standard components with a 4...20 mA current-loop interface
- connection and practical handling of components with a 4...20 mA 2-wire interface in a current loop
Specification
[1] use and practical handling of industrial components with a 4...20 mA current-loop interface
[2] various measuring principles for level measurement: level sensor, capacitive, and pressure sensor, piezo-resistive
[3] each sensor equipped with one analogue 4...20 mA interface and one HART interface
[4] current-loop connections led out with lab jacks on the front of the switch cabinet
[5] 2-channel line recorder with touchscreen operation
[6] USB interface to export the measurement data


Technical data
Pump
- max. head: 20,9m
- max. flow rate: 4,8m3/h
- power consumption: 0,73kW
- speed: 2850min-1
Level sensor (capacitive)
- calibrated: 40mm, 800mm
- length: 1016mm
- operating voltage: 24VDC
- HART output: 4...20mA
Pressure sensor (piezo-resistive)
- calibrated: 0mm WC, 800mm WC
- overload: 10bar
- operating voltage: 24VDC
- HART output: 4...20 mA
Measuring ranges
- pressure: 0...1bar
- level: 40...800mm
230V, 50Hz, 1 phase
230V, 60Hz, 1 phase, 120V, 60Hz, 1 phase
UL/CSA optional
LxWxH: 1280x790x2200mm
Weight: approx. 211kg